System performance of a split-type unit having R-22 and R-407C as working fluids

Chung szu Wei*, Sheih pei Lin, Chi-Chuan Wang

*Corresponding author for this work

研究成果: Conference article同行評審

13 引文 斯高帕斯(Scopus)

摘要

In this study, a drop-in system performance comparison of refrigerants R-22 and R-407C is reported. The test conditions include standard rating condition, overload condition, and low-temperature condition. It is found that the cooling capacity of R-407C is about 3% lower than that of the R-22 system, and the coefficient of performance (COP) for the R-407C system is 4% lower than that of the R-22 system. Meanwhile, the drop-in test results show that the condensing pressure for R-407C is 200 to 300 kPa higher than that of R-22.

原文English
頁(從 - 到)797-802
頁數6
期刊ASHRAE Transactions
103
發行號1
出版狀態Published - 1 一月 1997
事件Proceedings of the 1997 ASHRAE Winter Meeting - Philadelphia, PA, USA
持續時間: 26 一月 199729 一月 1997