T1 - Influence of variable heat load on the refrigerant distribution of a dual cold-plate system
AU - Yang, Kai Shing
AU - Yu, Kun Huang
AU - Liu, Chung Che
AU - Wang, Chi-Chuan
PY - 2008/12/1
Y1 - 2008/12/1
N2 - This study examines the refrigerant distribution of a dual cold plate system subject to the influence of heating load using a R-134a based vapor compression system with a nominal capacity ranging from 50-250 W. The cold plate is of identical configuration. Initially, test is performed under an equal heating load for each cold plate (70 W) which then gives rise to a uniform distribution and equal outlet superheat condition. For an unequal heating load, it is found that the distribution of mass flowrate subject to the influence of heating load is strongly related to the outlet states of the two cold plates. For the condition where one of the cold plate is in superheated state while the other is in saturated state, the mass flowrate for the fixed heating load is lower than that of smaller heating load, and the difference increases when the heating load gets smaller due to the influence of accelerational pressure drop. A maximum of 17% difference is seen at a loading ratio of 0.571 (40W/70W). For the condition where both outlet states of cold plate are at superheated states, the mass flowrate for the fixed heating load is marginally higher than that of the smaller heating load, and the difference is insensitive to the rise of heating load. For this situation, the effect of accelerational pressure is negligible, and it is mainly attributed to two-phase/single-phase distribution pertaining to the effect of heating load.
AB - This study examines the refrigerant distribution of a dual cold plate system subject to the influence of heating load using a R-134a based vapor compression system with a nominal capacity ranging from 50-250 W. The cold plate is of identical configuration. Initially, test is performed under an equal heating load for each cold plate (70 W) which then gives rise to a uniform distribution and equal outlet superheat condition. For an unequal heating load, it is found that the distribution of mass flowrate subject to the influence of heating load is strongly related to the outlet states of the two cold plates. For the condition where one of the cold plate is in superheated state while the other is in saturated state, the mass flowrate for the fixed heating load is lower than that of smaller heating load, and the difference increases when the heating load gets smaller due to the influence of accelerational pressure drop. A maximum of 17% difference is seen at a loading ratio of 0.571 (40W/70W). For the condition where both outlet states of cold plate are at superheated states, the mass flowrate for the fixed heating load is marginally higher than that of the smaller heating load, and the difference is insensitive to the rise of heating load. For this situation, the effect of accelerational pressure is negligible, and it is mainly attributed to two-phase/single-phase distribution pertaining to the effect of heating load.
KW - Cold plate
KW - Electronic cooling
KW - Refrigerant distribution
KW - Variable heating load
UR - http://www.scopus.com/inward/record.url?scp=77952636717&partnerID=8YFLogxK
U2 - 10.1115/ICNMM2008-62348
DO - 10.1115/ICNMM2008-62348
M3 - Conference contribution
AN - SCOPUS:77952636717
SN - 0791848345
SN - 9780791848340
T3 - Proceedings of the 6th International Conference on Nanochannels, Microchannels, and Minichannels, ICNMM2008
SP - 1431
EP - 1435
BT - Proceedings of the 6th International Conference on Nanochannels, Microchannels, and Minichannels, ICNMM2008
Y2 - 23 June 2008 through 25 June 2008
ER -