Experiments for suitability of plastic heat exchangers for dehumidification applications

Mohammed Amer*, Miao Ru Chen, Uzair Sajjad, Hafiz Muhammad Ali, Naseem Abbas, Ming-Chang Lu, Chi Chuan Wang

*Corresponding author for this work

研究成果: Article同行評審

7 引文 斯高帕斯(Scopus)

摘要

The present study conducted a series of experiments concerning the condensation of humid air used in a typical adsorption dehumidifier. The experiments were carried out with the standard ambient condition (27 °C dry bulb temperature and 21.2 °C wet bulb temperature)for the cold side. Yet the regeneration side (hot side)inlet temperature is 55 °C with RH% being 100%. Three novel plastic heat exchangers (plate plastic heat exchanger-PHX, bare tube plastic heat exchanger with asymmetry tube layout-BTHX, and round tube plastic heat exchanger with uniform tube layout-RTHX)were tested and compared experimentally. Test results, in terms of heat flux or heat transfer coefficient, show that the BTHX is superior to RTHX and PHX for offering additional condensate splashing mode. The splashing feature is especially beneficial for larger cold side flow rate since the plateau of heat transfer performance is moved toward larger cold side flow rate regime. The asymmetry tube geometry design (BTHX)shows even better heat transfer performance than the uniform tube bundle design (RTHX)for providing more space at the downstream of the tube bundle.

原文English
文章編號113827
期刊Applied Thermal Engineering
158
DOIs
出版狀態Published - 25 七月 2019