Condensation of R-134a on enhanced tubes

W. Y. Cheng*, Chi-Chuan Wang

*Corresponding author for this work

研究成果: Conference article同行評審

23 引文 斯高帕斯(Scopus)

摘要

Experiments were conducted to study the heat transfer characteristics of condensate on a vertical column of horizontal enhanced tubes. Three tubes arranged in a vertical column were set in stationary vapor. In the current experiment, six distinctly different enhanced tubes, including low-fin tubes of 26, 32, and 41 fins per inch (fpi) and three three-dimensional-fin tubes, were tested. In addition, a plain tube was also tested for comparison with Nusselt's theory. The working fluid used in the experiment is refrigerant R-134a. Average condensing heat transfer coefficients were obtained from the modified Wilson plot technique.

原文English
頁(從 - 到)809-817
頁數9
期刊ASHRAE Transactions
100
發行號2
出版狀態Published - 1 十二月 1994
事件Proceedings of the ASHRAE Annual Meeting - Orlando, FL, USA
持續時間: 25 六月 199429 六月 1994