An experimental study of plastic heat exchangers applicable for dehumidification

Mohammed Amer, Miao Ru Chen, Ming-Chang Lu, Chi Chuan Wang*

*Corresponding author for this work

研究成果: Conference article同行評審

摘要

Condensation of humid air on plastic heat exchangers is reported in this study. Three plastic HXs (plate type - PHX, asymmetry bare tube type - BTHX, and uniform round tube type - RTHX) were tested and compared in this experiment. The BTHX is superior to RTHX and PHX for offering additional condensate splashing mode and the splashing feature is especially beneficial when operated at a larger cold side flow rate since the plateau of the heat transfer performance is moved toward larger cold side flow rate regime. The asymmetry tube geometry design (BTHX) shows even better heat transfer performance than the uniform tube bundle design (RTHX).

原文English
頁(從 - 到)4463-4472
頁數10
期刊International Heat Transfer Conference
2018-August
DOIs
出版狀態Published - 1 一月 2018
事件16th International Heat Transfer Conference, IHTC 2018 - Beijing, China
持續時間: 10 八月 201815 八月 2018

指紋 深入研究「An experimental study of plastic heat exchangers applicable for dehumidification」主題。共同形成了獨特的指紋。