Air-water two-phase pressure drop in U-type wavy tubes

Ing Youn Chen*, Yee Kang Lai, Chi-Chuan Wang

*Corresponding author for this work

Research output: Contribution to journalArticlepeer-review

1 Scopus citations

Abstract

Two-phase frictional performance of air-water mixture flow in six horizontal U-type wavy tubes is presented. The inner diameters of the wavy tubes are 5.07 and 8.29 mm, whereas the curvature ratios span from 3.94 to ∼7.87. The two-phase superficial velocities for air and water are in the range of UL,S = 0.02-0.7 m/s and UG,S = 0.15-60 m/s. The measured pressure loss in bend included the loss in U bends and the loss caused by the distorted flow in the downstream straight tube. This leads to the definition of the equivalent frictional two-phase pressure gradient in the U bend. The ratio between the two-phase pressure gradient in the U-bend and the two-phase pressure gradient in the upstream straight tube is found in the range of 1.5-3 for most of the data. The ratios increase with gas quality due to consecutive accelerating/deaccelerating phenomenon caused by the wavy tube. The frictional two-phase multiplier in the U bend can be correlated by the use of the Chisholm correlation. By introduction of the Martinelli parameter and the liquid Froude number to the Chisholm correlation, a new correlation is proposed that can describe the present φB,L 2 data with a mean deviation of 13.9%.

Original languageEnglish
Pages (from-to)364-369
Number of pages6
JournalJournal of Thermophysics and Heat Transfer
Volume18
Issue number3
DOIs
StatePublished - 1 Jan 2004

Fingerprint Dive into the research topics of 'Air-water two-phase pressure drop in U-type wavy tubes'. Together they form a unique fingerprint.

Cite this